Hitachi Energy RTU500 CMU Firmware Update Authentication Bypass (CVE-2026-8065)
Published: 2026-11-25 • Researcher: murrez (GitHub repository, commit author "yoyo") / PoCbit (pocbit.org); origin reported by Dragos per CISA ICSA-26-279-06
- Severity
- Critical
- CVE
- CVE-2026-8065 (CISA ICSA-26-279-06)
- Category
- hardware
- Affected product
- Hitachi Energy RTU500 series CMU Firmware — firmware update endpoint of the RTU web interface (Configuration Management / firmware upload)
- Affected versions
- RTU500 series CMU Firmware versions 11.x and prior, all end-of-life (per Hitachi Energy via CISA ICSA-26-279-06 and Tenable OT plugin 506491). NVD lists no CPE version ranges for this CVE (record status: Awaiting Analysis).
- Disclosed
- 2026-11-25
- Patch status
- Unpatched
Tags
References
- https://nvd.nist.gov/vuln/detail/CVE-2026-8065
- https://www.cve.org/CVERecord?id=CVE-2026-8065
- https://publisher.hitachienergy.com/preview?DocumentID=8DBD000251&LanguageCode=en&DocumentPartId=&Action=Launch
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-279-06
- https://www.tenable.com/plugins/ot/506491
- https://github.com/murrez/CVE-2026-8065
- https://pocbit.org/pocs/cve-2026-8065
Archive entry
intelseclab/poc-archiveOn this page
Metadata
| Field | Value |
|---|---|
| Date Added | 2026-11-25 |
| Last Updated | 2026-09-29 |
| Author / Researcher | murrez (GitHub repository, commit author “yoyo”) / PoCbit (pocbit.org); origin reported by Dragos per CISA ICSA-26-279-06 |
| CVE / Advisory | CVE-2026-8065 (CISA ICSA-26-279-06) |
| Category | hardware |
| Severity | Critical |
| CVSS Score | 9.1 (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H) |
| Status | PoC |
| Tags | hitachi-energy, rtu500, ics, ot, firmware, authentication-bypass, cwe-306, unauthenticated, http-post, python |
| Related | N/A |
Affected Target
| Field | Value |
|---|---|
| Software / System | Hitachi Energy RTU500 series CMU Firmware — firmware update endpoint of the RTU web interface (Configuration Management / firmware upload) |
| Versions Affected | RTU500 series CMU Firmware versions 11.x and prior, all end-of-life (per Hitachi Energy via CISA ICSA-26-279-06 and Tenable OT plugin 506491). NVD lists no CPE version ranges for this CVE (record status: Awaiting Analysis). |
| Language / Platform | Embedded RTU firmware with an HTTP(S) management web server; PoC is Python 3 (requests/urllib3) plus an optional FOFA CSV helper, run from Linux, macOS or Windows |
| Authentication Required | No |
| Network Access Required | Yes — HTTP(S) reachability of the RTU500 web interface (default PoC probes 443, 8443, 80, 8080) |
Summary
CVE-2026-8065 is an authentication bypass in the firmware update endpoint of Hitachi Energy RTU500 series CMU firmware, affecting end-of-life versions 11.x and prior. The update function has no authentication check (CWE-306), so an unauthenticated attacker who can reach the RTU web interface can send a crafted POST request and upload arbitrary firmware. Successful exploitation can modify device functionality or compromise the integrity and availability of the RTU, which is deployed in substation and grid automation environments. The archived PoC fingerprints RTU500 web portals, probes candidate firmware update URIs, and sends a non-production probe upload to test whether an endpoint accepts unauthenticated firmware POSTs.
Vulnerability Details
Root Cause
The firmware update handler on the RTU500 CMU web interface does not enforce authentication or authorization before accepting an uploaded firmware image, which is CWE-306 (Missing Authentication for Critical Function). The endpoint is reachable without a session and processes the upload request itself, rather than rejecting it and redirecting to a login flow. Hitachi Energy states the affected code paths belong to legacy, end-of-life firmware releases (9.x was the version under review, and 11.x and prior are considered affected), and that the findings do not affect currently supported versions. The exact request path and the authentication check that is skipped are not documented in public advisories; the PoC therefore probes a list of candidate firmware URIs.
Attack Vector
An unauthenticated network attacker sends a crafted HTTP POST with a multipart firmware upload to the device’s firmware update endpoint (for example a Configuration Management or firmware upload path). No cookie, token or credentials are required. The archived PoC fingerprints the login page for RTU500 markers (rtu500, rtutil500, CMU firmware), then issues multipart POSTs with firmware-relevant form field names (file, firmware, upload, package and similar) to fourteen candidate paths, adding an X-Requested-With header, and treats a 2xx response with upload-accept heuristics as evidence that the unauthenticated upload was accepted.
Impact
Arbitrary firmware upload to a safety-critical remote terminal unit. Per the vendor and NVD, successful exploitation could modify device functionality or compromise the integrity or availability of the device, with CVSS impacts C:N/I:H/A:H. In an OT context this means a compromised substation RTU can be made to misreport or drop telemetry, be rendered unavailable, or run attacker-supplied code, depending on what the uploaded image does and whether firmware signature checks are enforced on the target build.
Environment / Lab Setup
OS: Linux (any host with Python 3.8+); optional Docker/Kali attacker VM
Target: Hitachi Energy RTU500 series CMU Firmware (end-of-life, 11.x or prior)
web interface, reachable over HTTPS/HTTP from the lab network
Attacker: Python 3.10+ host with requests/urllib3
Tools: python3, pip, curl, optional Burp Suite, optional FOFA CSV export
Note: The repository's --lab mode is a local mock RTU500, not real firmware.Setup Steps
| |
Proof of Concept
Step-by-Step Reproduction
- Install dependencies —
pip install -r requirements.txtinstalls requests and urllib3. - Validate the harness locally —
python3 poc.py --labstarts a mock RTU500 CMU server on 127.0.0.1:8765, fingerprints it, and POSTs the probe blob. This only proves the detection logic works; it does not reproduce the vendor bug. - Fingerprint the target —
python3 poc.py -u https://<rtu-host> --mode checkresolves HTTP versus HTTPS and the common ports, looks for RTU500 markers in the login page, extracts a CMU firmware version if present, and GET-probes the candidate firmware paths. - Dry-run the upload path —
python3 poc.py -u https://<rtu-host> --mode exploit --dry-runperforms GET probes only and reports any API-like firmware path; no POST is sent. - Send the unauthenticated probe —
python3 poc.py -u https://<rtu-host> --mode exploitsends multipart POSTs carrying the probe blob (marker POCBIT-8065-FW-PROBE plus 512 NUL bytes) with no session cookie. A hit is reported when a candidate endpoint returns 2xx with upload-accept heuristics. - Record the result — the JSON row is printed and, in mass mode, written to the results JSONL plus exploited.txt. The probe blob is deliberately not a valid CMU flash image, so nothing is flashed.
Exploit Code
See
poc.pyin this folder; the target-list helper is_format_fofa.pyand the upstream write-up isupstream-README.md.
The core unauthenticated probe is:
| |
Expected Output
| |
Against a real RTU the same status and a 2xx hit response (or upload-success text in the body) are the success signal; anything else is reported as not_rtu500, dry_run_no_firmware_api or upload_not_accepted.
Detection & Indicators of Compromise
- POST requests to firmware upload/update paths (
/api/firmware/update,/firmware/upload,/ConfigurationManagement/Firmware,/FileUpload/Firmware, and similar) that arrive without a prior successful login or session cookie. - Multipart bodies with a
.fwfilename, the markerPOCBIT-8065-FW-PROBE, or a file part containing almost entirely NUL padding immediately after a small text header. - Requests carrying
X-Requested-With: XMLHttpRequestagainst firmware endpoints, and the PoC user agent suffixPoCbit-OT (+https://pocbit.org). - Sequential GET sweeps across many candidate firmware paths from one source, followed by POSTs — typical of the check-then-exploit and mass modes.
- Device-side evidence: unexpected firmware version change, reboot or loss of configuration, firmware integrity or signature-check alerts, HTTP 200 upload acknowledgements in the web server log without a login entry.
Example web server / IDS signature:
| |
SIEM example (proxy/access log pattern):
| |
Remediation
| Action | Detail |
|---|---|
| Patch | Upgrade RTU500 series CMU firmware to 12.7.8 or 13.9.1 (or later) as stated in the Hitachi Energy advisory and CISA ICSA-26-279-06. End-of-life versions 11.x and prior receive no fix and should be replaced or upgraded off the unsupported branch. |
| Workaround | No configuration toggle is documented to disable the vulnerable update function. Reduce exposure by segmenting the RTU management network, restricting the web interface to a jump host with MFA, and blocking unauthenticated POSTs to firmware paths at the OT firewall/WAF until the firmware is upgraded. |
| Config Hardening | Follow the vendor’s general mitigation factors: defense-in-depth segmentation for substation networks, IEC 62351-3 style secure communications, controlled and monitored firmware management, alerting on firmware writes and device configuration changes, and periodic verification that management interfaces are not internet-reachable. |
References
Notes
Auto-ingested from https://github.com/murrez/CVE-2026-8065 on 2026-11-25.
Review verdict: Ingested as a limited proof-of-concept, not a weaponized exploit. The repository is not a pure detector: exploit mode performs an actual unauthenticated multipart firmware POST to firmware update endpoints and reports acceptance, so it is exploit code rather than a scanner. It is nonetheless limited — the upload payload is a 536-byte marker-plus-NUL probe blob, not a valid CMU flash image; the vendor has not published the exact endpoint URI, so fourteen guessed paths and guessed field names are rotated; success is inferred from HTTP status and upload-accept heuristics; and the --lab mock is self-authored, so a green lab result only proves the client logic. Its --mode check and FOFA mass modes are reconnaissance and scanning helpers that ship alongside the exploit.
Accuracy notes: Hitachi Energy via CISA lists CMU firmware 11.x and prior (all end-of-life) as affected and names 12.7.8 / 13.9.1 or later as the fix. The upstream repository README instead mentions 9.0 and 12.0 version lines and a 13.8.2+ patch; this entry follows the vendor/CISA statement. NVD still marks the record Awaiting Analysis and provides no CPE ranges, which is why Versions Affected is sourced from the CISA advisory. CVSS 9.1 and the vector are consistent across NVD, CISA and the repository. Tenable’s plugin notes no known public exploit at the time of writing.
Licensing: The repository is MIT licensed (Copyright (c) 2026 yoyo). The copied poc.py carries the required archived-for-research header; attribution is preserved via upstream-README.md and LICENSE.
Handling: The PoC was not executed against any device while archiving, and no flash image was produced. The included probe blob is non-destructive but still constitutes an unauthenticated upload attempt; only run it against RTU500 hardware in an isolated lab or under a vendor-approved engagement, and never against live grid equipment. The --force flag skips the RTU500 fingerprint and should not be used against production networks.
| |